p2200[0...n]
BI: Technology controller enable / Tec_ctrl enable
Access level: 2
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
p2201[0...n]
CO: Technology controller fixed value 1 / Tec_ctrl fix val1
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2202[0...n]
CO: Technology controller fixed value 2 / Tec_ctr fix val 2
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2203[0...n]
CO: Technology controller fixed value 3 / Tec_ctr fix val 3
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the value for fixed value 3 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2204[0...n]
CO: Technology controller fixed value 4 / Tec_ctr fix val 4
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the value for fixed value 4 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 7958
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7950, 7951
Factory setting
10.00 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7950, 7951
Factory setting
20.00 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7950, 7951
Factory setting
30.00 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7950, 7951
Factory setting
40.00 [%]
363