Siemens SINAMICS G120 List Manual page 35

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

08
09
10
11
12
15
16
17
18
19
20
21
25
26
27
28
29
30
31
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching-on inhibited".
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 04 =1 (armature short-circuit active), if:
- the signal source in p1230 has a 1 signal.
Bit 05, Bit 06: Being prepared
Bit 08 = 1 (enable signal missing), if:
- safety functions have been enabled and STO is active.
- STO is selected via onboard terminals or PROFIsafe.
- a safety-relevant signal is present with STOP A response.
- the "STO via terminals at the Power Module" function is selected.
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
Bit 10 = 1 (enable signal missing), if:
- the signal source in p1140 is a 0 signal.
Bit 11 = 1 (enable signal missing) if the speed setpoint is frozen, because:
- the signal source in p1141 is a 0 signal.
- the speed setpoint is entered from jogging and the two signal sources for jogging, bit 0 (p1055) and bit 1 (p1056)
have a 1 signal.
Bit 12 = 1 (enable signal missing), if:
- the signal source in p1142 is a 0 signal.
- When activating the function module "basic positioner" (r0108.4 = 1), the signal source in p1142 is set to a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enabled if the fault is removed and was acknowledged and the
"switching-on inhibited" withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- commissioning mode is selected (p0010 > 0).
- there is an OFF2 fault response.
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Safety enable missing
Infeed enable missing
Ramp-function generator enable missing
Ramp-function generator start missing
Setpoint enable missing
QuickStop enable missing
OFF1 enable internal missing
OFF2 enable internal missing
OFF3 enable internal missing
Pulse enable internal missing
Armature short-circuit/DC braking internal
enable missing
STOP2 enable internal missing
Function bypass active
Drive inactive or not operational
De-magnetizing not completed
Brake open missing
Cooling unit ready signal missing
Speed controller inhibited
Jog setpoint active
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
35

Hide quick links:

Advertisement

loading