Siemens SINAMICS G120 List Manual page 215

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

06
07
08
09
10
11
12
13
14
15
Note:
For bit 00 ... 09:
Used to control internal sequences during the flying restart.
Depending on the motor type (p0300), the number of active bits differs.
For bits 10 ... 15:
Are used to monitor the flying restart sequence.
p1206[0...9]
Automatic restart faults not active / AR fault not act
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets faults for which automatic restart should not be effective.
Dependency:
The setting is only effective for p1210 = 6, 16, 26.
Refer to: p1210
p1210
Automatic restart mode / AR mode
Access level: 2
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the automatic restart mode (AR).
The parameters must be saved in the non-volatile memory p0971 = 1 in order that the setting becomes effective.
Value:
0:
1:
4:
6:
14:
16:
26:
Recommendation:
For brief line supply failures, the motor shaft may still be rotating when restarting. The "flying restart" function (p1200)
might need to be activated to restart while the motor shaft is still rotating.
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Operator Panel in the LOCAL mode, then there is no automatic start.
For p1210 = 14, 16, a manual acknowledgment is required for an automatic restart.
Refer to: p0840, p0857
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is switched on
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is present again. This automatic switching-on operation can only be
interrupted by withdrawing the ON command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). When faults
are present, therefore, the parameter cannot be changed.
For p1210 > 1, the motor is automatically started.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Speed adaptation circuit set I component to
0
Current control on
Isd_set = 0 A
Frequency held
Search in the positive direction
Search Started
Current impressed
Search interrupted
Speed adaptation circuit deviation = 0
Speed control activated
Inhibit automatic restart
Acknowledge all faults without restarting
Restart after line supply failure w/o additional start attempts
Restart after fault with additional start attempts
Restart after line supply failure following man. acknowledgment
Restart after fault following manual acknowledgment
Acknowledging all faults and reclosing for an ON command
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
26
2 Parameters
2.2 List of parameters
No
No
No
No
No
No
No
No
No
No
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
-
-
-
-
-
-
-
-
-
-
215