2 Parameters
2.2 List of parameters
p8805
Identification and maintenance 4 configuration / I&M 4 config
CU250S_V_PN
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the configuration for the content of identification and maintenance 4 (I&M 4, p8809).
Value:
0:
1:
Dependency:
For p8805 = 0, if the user writes at least one value in p8809[0...53], then p8805 is automatically set to = 1.
When p8805 is reset = 0, then the content of the factory setting is set in p8809.
Note:
For p8805 = 0:
PROFINET I&M 4 (p8809) contains the information for the SI change tracking.
For p8805 = 1:
PROFINET I&M 4 (p8809) contains the values written by the user.
p8806[0...53]
Identification and Maintenance 1 / I&M 1
CU250S_V_PN
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Parameters for the PROFINET data set "Identification and Maintenance 1" (I&M 1).
This information is known as "System identifier" and "Location identifier".
Dependency:
Refer to: p8807, p8808
Notice:
Only characters belonging to the standard ASCII character set may be used (32 dec to 126 dec).
Note:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
For p8806[0...31]:
System identifier.
For p8806[32...53]:
Location identifier.
p8807[0...15]
Identification and Maintenance 2 / I&M 2
CU250S_V_PN
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Parameters for the PROFINET data set "Identification and Maintenance 2" (I&M 2).
This information is known as "Installation date".
Dependency:
Refer to: p8806, p8808
Note:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
For p8807[0...15]:
Dates of installation or first commissioning of the device with the following format options (ASCII):
YYYY-MM-DD
or
YYYY-MM-DD hh:mm
- YYYY: year
- MM: month 01 ... 12
- DD: day 01 ... 31
- hh: hours 00 ... 23
- mm: minutes 00 ... 59
Separators must be placed between the individual data, i.e. a hyphen '-', space ' ' and colon ':'.
530
Standard value for I&M 4 (p8809)
User value for I&M 4 (p8809)
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890

Hide quick links:

Advertisement

loading