Download Print this page

Siemens SINAMICS G120 List Manual page 194

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
Refer to: p1071, r1073, r1078
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1071[0...n]
CI: Main setpoint scaling / Main setp scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the main setpoint.
r1073
CO: Main setpoint effective / Main setpoint eff
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the effective main setpoint.
The value shown is the main setpoint after scaling.
p1075[0...n]
CI: Supplementary setp / Suppl setp
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the supplementary setpoint.
Dependency:
Refer to: p1076, r1077, r1078
p1076[0...n]
CI: Supplementary setpoint scaling / Suppl setp scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the supplementary setpoint.
r1077
CO: Supplementary setpoint effective / Suppl setpoint eff
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
194
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3001, 3030
Factory setting
1
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3030
Factory setting
- [rpm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3001, 3030
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3001, 3030
Factory setting
1
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3030
Factory setting
- [rpm]