2 Parameters
2.2 List of parameters
p2006
Reference temperature / Ref temp
Access level: 3
Can be changed: T
Unit group: 21_1
Min
50.00 [°C]
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
p2007
Reference acceleration / a_ref
Access level: 4
Can be changed: T
Unit group: -
Min
0.01 [rev/s²]
Description:
Sets the reference quantity for acceleration rates.
All acceleration rates specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference acceleration is calculated as follows:
p2007 = p2000 / 1 [s]
p2010
Comm IF baud rate / Comm baud
Access level: 3
Can be changed: T
Unit group: -
Min
6
Description:
Sets the baud rate for the commissioning interface (USS, RS232).
Value:
6:
7:
8:
9:
10:
11:
12:
Note:
COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
p2011
Comm IF address / Comm add
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the address for the commissioning interface (USS, RS232).
Note:
The parameter is not influenced by setting the factory setting.
314
9600 baud
19200 baud
38400 baud
57600 baud
76800 baud
93750 baud
115200 baud
Calculated: p0340 = 1
Scaling: -
Unit selection: p0505
Max
300.00 [°C]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
500000.00 [rev/s²]
Calculated: -
Scaling: -
Unit selection: -
Max
12
Calculated: -
Scaling: -
Unit selection: -
Max
31
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
100.00 [°C]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.01 [rev/s²]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
12
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
2
SINAMICS G120 CU250S-2 Control Units