2 Parameters
2.2 List of parameters
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
p0724
CU digital inputs debounce time / CU DI t_debounce
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [ms]
Description:
Sets the debounce time for digital inputs.
Note:
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
p0728
CU set input or output / CU DI or DO
Access level: 1
Can be changed: T
Unit group: -
Min
-
Description:
Sets the bidirectional digital inputs/outputs as an input or output.
Bit field:
Bit
24
25
26
27
Note:
DI/DO: Bidirectional Digital Input/Output
r0729
CU digital outputs access authority / CU DO acc_auth
Access level: 1
Can be changed: -
Unit group: -
Min
-
Description:
Displays the access authority at the digital outputs.
Bit = 1:
The control has access authority to the digital output via PROFIBUS or direct access.
Bit = 0:
The drive has access authority to the digital output or the digital input/output is not set as digital output or is not
available.
Bit field:
Bit
00
01
02
24
25
26
27
Dependency:
Refer to: p0728, p0738, p0739, p0740, p0741, r0747, p0748
Note:
The DI/DO must be connected as output (p0728).
DI/DO: Bidirectional Digital Input/Output
140
Signal name
DI/DO 24 (T. 51)
DI/DO 25 (T. 52)
DI/DO 26 (T. 53)
DI/DO 27 (T. 54)
Signal name
DO 0 (NO: T. 19 / NC: T. 18)
DO 1 (NO: T. 21)
DO 2 (NO: T. 24 / NC: T. 23)
DI/DO 24 (T. 51)
DI/DO 25 (T. 52)
DI/DO 26 (T. 53)
DI/DO 27 (T. 54)
Calculated: -
Scaling: -
Unit selection: -
Max
20.000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Output
Output
Output
Output
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
High
High
High
High
High
High
High
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
4.000 [ms]
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2230, 2231
Factory setting
0000 0000 0000 0000 0000 0000 0000
0000 bin
0 signal
Input
Input
Input
Input
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2030, 2031
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890