2 Parameters
2.2 List of parameters
r3313
Efficiency optimization 2 optimum flux / Optimum flux
Access level: 3
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the calculated, optimum flux.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1401, p3315, p3316
Note:
The function is activated via p1401.14 = 1.
p3315[0...n]
Efficiency optimization 2 minimum flux limit value / Min flux lim val
Access level: 3
Can be changed: U, T
Unit group: -
Min
10.0 [%]
Description:
Sets the minimal limit value for the calculated optimum flux.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1401, r3313, p3316
Note:
The function is activated via p1401.14 = 1.
p3316[0...n]
Efficiency optimization 2 maximum flux limit value / Max flux lim val
Access level: 3
Can be changed: U, T
Unit group: -
Min
10.0 [%]
Description:
Sets the maximum limit value for the calculated optimum flux.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1401, r3313, p3315
Note:
The function is activated via p1401.14 = 1.
p3320[0...n]
Fluid flow machine power point 1 / Fluid_mach P1
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 1 as a [%].
The characteristic comprises the following value pairs:
Power (P) / speed (n)
p3320 / p3321 --> point 1 (P1 / n1)
p3322 / p3323 --> point 2 (P2 / n2)
p3324 / p3325 --> point 3 (P3 / n3)
p3326 / p3327 --> point 4 (P4 / n4)
p3328 / p3329 --> point 5 (P5 / n5)
Dependency:
Refer to: r0041, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
450
Calculated: -
Scaling: r2004
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
200.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
200.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6722, 6837
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6722, 6837
Factory setting
50.0 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6722, 6837
Factory setting
110.0 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
25.00
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890