2 Parameters
2.2 List of parameters
p1142[0...n]
BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU250S_V
Access level: 3
CU250S_V_CAN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency:
Refer to: p1140, p1141
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
p1142[0...n]
BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU250S_V (Position
Access level: 3
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency:
Refer to: p1140, p1141
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
p1143[0...n]
BI: Ramp-function generator, accept setting value / RFG accept set v
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
208
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 3060, 3070
Factory setting
0
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890