Siemens SINAMICS G120 List Manual page 61

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value:
0:
1:
2:
10:
13:
17:
19:
100:
101:
104:
105:
107:
108:
271:
277:
10000: Motor with DRIVE-CLiQ
10001: Motor with DRIVE-CLiQ 2nd data set
Dependency:
When selecting p0300 = 10 ... 19, parameters p0335, p0626, p0627, and p0628 of the thermal motor model are pre-
assigned as a function of p0307 and p0311.
For p0096 = 1 (Standard Drive Control) synchronous motor types cannot be selected.
Caution:
If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Notice:
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters
that are associated with this list cannot be changed (write protection). The write protection is canceled if the motor
type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 1 for p0301 = 1xxxx). Write protection is
automatically canceled when the results of motor data identification are copied to the motor parameters.
The motor type of a catalog motor corresponds to the upper three digits of the code number or the following
assignment (if the particular motor type is listed):
Type/code number ranges
100 / 100xx, 110xx, 120xx, 130xx, 140xx, 150xx
104 / 104xx, 114xx, 124xx
107 / 107xx, 117xx, 127xx,
108 / 108xx, 118xx, 128xx, 138xx, 148xx, 158xx
271 / 271xx, 281xx
277 / 277xx, 287xx, 297xx
Note:
Motor without DRIVE-CLiQ: Once the Control Unit has been switched on for the first time or if the factory settings
have been defined accordingly, the motor type is pre-configured as induction motor (p0300 = 1).
With p0300 = 10000, for a motor with DRIVE-CLiQ, the motor parameters are automatically downloaded, with p0300
= 10001, the motor parameters of a second data set (if available).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Motor types with a value below p0300 < 100 correspond to the selection of a third-party motor. When appropriately
selected, this means that the motor parameters are pre-assigned the settings for a third-party motor.
This also applies for parameters for a motor with DRIVE-CLiQ. In this case p0300 can only be set to p0300 = 10000
or 10001 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number)
in order to be able to cancel the write protection.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
No motor
Induction motor
Synchronous motor
1LE1 induction motor (not a code number)
1LG6 induction motor (not a code number)
1LA7 induction motor (not a code number)
1LA9 induction motor (not a code number)
1LE1 induction motor
1PC1 induction motor
1PH4 induction motor
1LE5 induction motor
1PH7 induction motor
1PH8 induction motor
1FG1 synchronous geared motor without encoder
1FK7 synchronous motor without encoder
2 Parameters
2.2 List of parameters
61