2 Parameters
2.2 List of parameters
r0623
Rs identification stator resistance after switch on again / Rs-id Rs aft sw-on
Access level: 4
Can be changed: -
Unit group: -
Min
- [ohm]
Description:
Displays the stator resistance determined using the Rs identification after switching on again.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0621, p0622
p0625[0...n]
Motor ambient temperature during commissioning / Mot T_ambient
Access level: 3
Can be changed: C(3), U, T
Unit group: 21_1
Min
-40 [°C]
Description:
Defines the ambient temperature of the motor for calculating the motor temperature model.
Dependency:
Refer to: p0350, p0354
Note:
The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
p0626[0...n]
Motor overtemperature, stator core / Mot T_over core
Access level: 4
Can be changed: C(3), U, T
Unit group: 21_2
Min
10 [K]
Description:
Defines the rated overtemperature of the stator iron referred to ambient temperature in the motor temperature model
2 (p0612.1 = 1).
Dependency:
For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0627[0...n]
Motor overtemperature, stator winding / Mot T_over stator
Access level: 2
Can be changed: C(3), U, T
Unit group: 21_2
Min
15 [K]
Description:
Defines the rated overtemperature of the stator winding referred to the ambient temperature.
- motor temperature model 1 (I2t, p0612.0 = 1):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
p0605 is of significance for the rated temperature.
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
Overtemperature at the rated operating point.
- motor temperature model 2 (p0612.1 = 1):
Overtemperature at the rated operating point.
134
Calculated: -
Scaling: -
Unit selection: -
Max
- [ohm]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: p0505
Max
80 [°C]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: p0505
Max
200 [K]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: p0505
Max
200 [K]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [ohm]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017, 8018
Factory setting
20 [°C]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8018
Factory setting
50 [K]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017, 8018
Factory setting
80 [K]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890