2 Parameters
2.2 List of parameters
Value:
0:
1:
2:
Dependency:
Refer to: p9495, p9497, p9498, p9499
Refer to: A01318, A01507
Note:
The BI/CI parameters involved are listed in p9498[0...29] (signal sink).
The associated BO/CO parameters are listed in p9499[0...29] (signal source).
After p9496 = 1, 2 the following applies:
- p9497 = 0
- p9496 = 0
p9497
BICO interconnections to deactivated drive objects number / Interconn obj qty
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Displays the number of saved BICO interconnections to drive objects that are either not capable of operation or have
been deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Dependency:
Refer to: p9495, p9496, p9498, p9499
Refer to: A01318, A01507
p9498[0...29]
BICO BI/CI parameters to deactivated drive objects / BI/CI to deact obj
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Displays the saved BI/CI parameters (signal sink), whose source is located on drive objects that are either not
capable of operation or have been deactivated.
Dependency:
Refer to: p9495, p9496, p9497, p9499
Refer to: A01318, A01507
Note:
A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
p9499[0...29]
BICO BO/CO parameters to deactivated drive objects / BO/CO to deact obj
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Displays the saved BO/CO parameters (signal source), which are located on drive objects that are either not capable
of operation or have been deactivated.
Dependency:
Refer to: p9495, p9496, p9497, p9498
Refer to: A01318, A01507
Note:
A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
554
Inactive
Restore the interconnections from the list
Delete the interconnections from the list
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890