2 Parameters
2.2 List of parameters
Bit 18 = 1 (enable signal missing), if:
- OFF3 has still not been completed or an OFF3 fault response is present.
Bit 19 = 1 (internal pulse enable missing), if:
- synchronization is running between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle.
Bit 20 =1 (internal armature short-circuit active), if:
- the drive is not in the state "S4: Operation" or "S5x" (refer to function diagram 2610).
- the internal pulse enable is missing (r0046.19 = 0).
Bit 21 = 1 (enable signal missing), if:
The pulses have been enabled and the speed setpoint has still not been enabled, because:
- the holding brake opening time (p1216) has still not expired.
- the motor has still not been magnetized (induction motor).
- the encoder has not been calibrated (U/f vector and synchronous motor).
Bit 22: Being prepared
Bit 26 = 1 (enable signal missing), if:
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
- the function "parking axis" is selected (BI: p0897 = 1 signal)..
- all power units of a parallel connection are deactivated (p0125, p0895).
Bit 27 = 1 (enable signal missing), if:
- de-magnetizing has still not been completed (only for vector).
Bit 28 = 1 (enable signal missing), if:
- the holding brake is closed or has still not been opened.
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
Bit 30 = 1 (speed controller inhibited), if one of the following reasons is present:
- a 0 signal is available via binector input p0856.
- the function generator with current input is active.
- the measuring function "current controller reference frequency characteristic" is active.
- the pole position identification is active.
- motor data identification is active (only certain steps).
Bit 31 = 1 (enable signal missing), if:
- the speed setpoint from jog 1 or 2 is entered.
r0047
Motor data identification and speed controller optimization / MotID and n_opt
Access level: 1
Can be changed: -
Unit group: -
Min
0
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed controller
optimization (rotating measurement).
Value:
0:
115:
120:
140:
150:
170:
195:
200:
220:
230:
240:
250:
260:
270:
290:
300:
36
No measurement
Measurement q leakage inductance (part 2)
Speed controller optimization (vibration test)
Calculate speed controller setting
Measurement moment of inertia
Measurement magnetizing current and saturation characteristic
Measurement q leakage inductance (part 1)
Rotating measurement selected
identification leakage inductance
Identification rotor time constant
Identification stator inductance
Identification stator inductance LQLD
Identification circuit
Identification stator resistance
Identification valve lockout time
Stationary measurement selected
Calculated: -
Scaling: -
Unit selection: -
Max
300
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
-
SINAMICS G120 CU250S-2 Control Units