Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Note:
Corresponds to the CANopen object 1800 hex.
Transmission types 0, 1 ... F0, FE and FF can be set.
p2048: CANopen sampling time
PDO: Process Data Object
p8721[0...4]
CAN Transmit PDO 2 / Transmit PDO 2
CU250S_V_CAN
Access level: 3
Can be changed: C(3), T
Unit group: -
Min
0000 hex
Description:
Sets the communication parameters for CANopen Transmit Process Data Object 2 (TPDO 2).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Notice:
For inhibit time and event timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note:
Corresponds to the CANopen object 1801 hex.
Transmission types 0, 1 ... F0, FE and FF can be set.
p2048: CANopen sampling time
PDO: Process Data Object
p8722[0...4]
CAN Transmit PDO 3 / Transmit PDO 3
CU250S_V_CAN
Access level: 3
Can be changed: C(3), T
Unit group: -
Min
0000 hex
Description:
Sets the communication parameters for CANopen Transmit Process Data Object 3 (TPDO 3).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Notice:
For inhibit time and event timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note:
Corresponds to the CANopen object 1802 hex.
Transmission types 0, 1 ... F0, FE and FF can be set.
p2048: CANopen sampling time
PDO: Process Data Object
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
C000 06DF hex
Calculated: -
Scaling: -
Unit selection: -
Max
C000 06DF hex
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: 9208, 9210
Factory setting
[0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex
Data type: Unsigned32
Dyn. index: -
Func. diagram: 9208, 9210
Factory setting
[0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex