Siemens SINAMICS G120 List Manual page 205

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Note:
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up
completed. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of
the previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new
setpoint.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint. For
the setpoint change there is no rounding-off.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
Access level: 2
Can be changed: C(1), U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
Note:
The ramp-up time is set in p1120.
p1139[0...n]
CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
Refer to: p1121
Note:
The ramp-down time is set in p1121.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
5400.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
30.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
30.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3060, 3070
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3070
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3070
Factory setting
0.000 [s]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3060, 3070
Factory setting
1
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3060, 3070
Factory setting
1
205