2 Parameters
2.2 List of parameters
p60122
PROFIdrive SIC telegram selection / Pd SIC telegr
CU250S_V_DP
Access level: 3
CU250S_V_PN
Can be changed: T
Unit group: -
Min
700
Description:
Sets the telegram for the Safety Info Channel (SIC).
The SIC telegram p60122 is attached directly to the PZD telegram p0922/p2079.
Value:
700:
999:
Dependency:
Refer to: p0922, p2071, p2079
Note:
The clearance to the PZD telegram can be increased using p2071.
After changing p0922/p2079 or p2071, then p60122 must be set again.
The telegram interconnections can only be changed if p60122 and p0922 are both set to 999.
r61000[0...239]
PROFINET Name of Station / PN Name of Station
CU250S_V_PN
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays PROFINET Name of Station.
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
r61001[0...3]
PROFINET IP of Station / PN IP of Station
CU250S_V_PN
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays PROFINET IP of Station.
694
Supplementary telegram 700, PZD-0/3
Free telegram configuration with BICO
Calculated: -
Scaling: -
Unit selection: -
Max
999
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: Integer16
Dyn. index: -
Func. diagram: 2423
Factory setting
999
Data type: Unsigned8
Dyn. index: -
Func. diagram: 2410
Factory setting
-
Data type: Unsigned8
Dyn. index: -
Func. diagram: 2410
Factory setting
-
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890