2 Parameters
2.2 List of parameters
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
CU250S_V_DP
Access level: 3
CU250S_V_PN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
CU250S_V
Access level: 3
CU250S_V_CAN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1058[0...n]
Jog 1 speed setpoint / Jog 1 n_set
Access level: 2
Can be changed: T
Unit group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
p1059[0...n]
Jog 2 speed setpoint / Jog 2 n_set
Access level: 2
Can be changed: T
Unit group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
192
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501, 3030
Factory setting
[0] 0
[1] 722.1
[2] 0
[3] 0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501, 3030
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3001, 3030
Factory setting
150.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3001, 3030
Factory setting
-150.000 [rpm]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890