Siemens SINAMICS G120 List Manual page 485

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

r5389.0...8
CO/BO: Mot_temp status word faults/alarms / Mot_temp ZSW F/A
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
Display and BICO output for faults and alarms of the motor temperature monitoring.
Bit field:
Bit
00
01
02
04
05
08
Dependency:
Refer to: r0034, p0612, r0632
Refer to: F07011, A07012, A07910
Note:
For bit 00, 04:
The motor temperature is measured using a temperature sensor (p0600, p0601). When the bit is set, a high
temperature is identified, and a corresponding signal is additionally output.
For bit 01, 05:
The motor temperature is monitored based on a temperature model (p0612). When the bit is set, a high temperature
is identified, and a corresponding signal is additionally output.
For bit 02:
The encoder temperature is measured using a temperature sensor. When the bit is set, a high temperature is
identified, and a corresponding signal is additionally output.
For bit 08:
When reaching the motor temperature alarm threshold, reduction of the maximum current is set as response (p0610
= 1). When the bit is set, reduction of the maximum current is active.
p5390[0...n]
Mot_temp_mod 1/3 alarm threshold / A thresh
Access level: 2
Can be changed: C(3), U, T
Unit group: 21_1
Min
0.0 [°C]
Description:
Sets the alarm threshold for monitoring the motor temperature for motor temperature models 1 and 3.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- Alarm A07012 is output after the alarm threshold is exceeded.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0605 to p5390.
The following applies for temperature model 3:
- after the alarm threshold is exceeded, alarm A07012 is output and a calculated delay time (t = p5371/p5381) is
started.
- if the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency:
Refer to: r0034, p0605, p0612, r0632, p5391
Refer to: F07011, A07012, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Signal name
Motor temperature measurement fault
active
Motor temperature model fault active
Encoder temperature measurement fault
active
Motor temperature measurement alarm
active
Motor temperature measurement alarm
active
Current reduction active
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: p0505
Max
200.0 [°C]
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8016
Factory setting
-
0 signal
No
No
No
No
No
No
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017
Factory setting
110.0 [°C]
FP
-
-
-
-
-
-
485