Dependency:
Refer to: r0024
Note:
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
r0067
CO: Output current maximum / Current max
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Display and connector output for the maximum output current of the power unit.
Dependency:
The maximum output current is determined by the parameterized current limit and the motor and converter thermal
protection.
Refer to: p0290, p0640
r0068[0...1]
CO: Absolute current actual value / I_act abs val
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Displays actual absolute current.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
Refer to: r0027
Notice:
The value is updated with the current controller sampling time.
Note:
Absolute current value = sqrt(Iq^2 + Id^2)
The absolute value of the current actual value is available smoothed (r0027 with 300 ms, r0068[1] with p0045) and
unsmoothed (r0068[0]).
r0069[0...8]
CO: Phase current actual value / I_phase act val
Access level: 4
Can be changed: -
Unit group: 6_5
Min
- [A]
Description:
Display and connector output for the measured actual phase currents as peak value.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
[3] = Phase U offset
[4] = Phase V offset
[5] = Phase W offset
[6] = Total U, V, W
[7] = Alpha component
[8] = Beta component
Note:
In indices 3 ... 5, the offset currents of the 3 phases, which are added to correct the phase currents, are displayed.
The sum of the 3 corrected phase currents is displayed in index 6.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [A]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300, 6640, 6724
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300, 6714, 6799,
7017, 8017, 8021, 8022
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6730, 6731
Factory setting
- [A]