r2273
CO: Technology controller system deviation / Tec_ctrl sys_dev
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: -
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
- [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Displays the system deviation between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
p2274
Technology controller differentiation time constant / Tec_ctrl D comp T
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.000 [s]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
p2280
Technology controller proportional gain / Tec_ctrl Kp
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.000
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the proportional gain (P component) of the technology controller.
Note:
p2280 = 0: The proportional gain is disabled.
p2285
Technology controller integral time / Tec_ctrl Tn
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.000 [s]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Notice:
The following applies for p2251 = 0:
If the output of the technology controller lies within the range of a suppression (skip) bandwidth (p1091 ... p1094,
p1101) or below the minimum speed (p1080), the integral component of the controller is held so that the controller
temporarily works as a P controller. This is necessary in order to prevent the controller from behaving in an unstable
manner, as the ramp-function generator switches to the parameterized up and down ramps (p1120, p1121) at the
same time in order to avoid setpoint steps. This state can be exited or avoided by changing the controller setpoint or
by using the start speed (= minimum speed).
Note:
When the controller output reaches the limit, the I component of the controller is held.
p2285 = 0:
The integral time is disabled and the I component of the controller is reset.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.000
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
30.000 [s]