2 Parameters

2.2 List of parameters

Note:
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
p0010
Drive commissioning parameter filter / Drv comm. par_filt
Access level: 1
Can be changed: C(1), T
Unit group: -
Min
0
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
3:
4:
5:
11:
15:
17:
25:
29:
30:
39:
49:
95:
Dependency:
Refer to: r3996
Note:
The drive can only be powered up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0015
Macro drive unit / Macro drv unit
CU250S_V_DP
Access level: 1
CU250S_V_PN
Can be changed: C, C(1)
Unit group: -
Min
0
Description:
Runs the corresponding macro files.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
Macros available as standard are described in the technical documentation of the particular product.
26
Ready
Quick commissioning
Power unit commissioning
Motor commissioning
Encoder commissioning
Technological application/units
Function modules
Data sets
Basic positioner commissioning
Position control commissioning
Only Siemens internal
Parameter reset
Only Siemens internal
Only Siemens internal
Safety Integrated commissioning
Calculated: -
Scaling: -
Unit selection: -
Max
95
Calculated: -
Scaling: -
Unit selection: -
Max
999999
Data type: Integer16
Dyn. index: -
Func. diagram: 2800, 2818
Factory setting
1
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
7
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890