Signal sources for ZDSW2 im Interface Mode SINAMICS (p2038 = 0)
Signal
ZSW2.0
1 = DDS effective bit 0
ZSW2.1
1 = DDS effective bit 1
ZSW2.2
Reserved
ZSW2.3
Reserved
ZSW2.4
Reserved
ZSW2.5
1 = Alarm class bit 0
ZSW2.6
1 = Alarm class bit 1
ZSW2.7
Reserved
ZSW2.8
1 = Travel to fixed stop active
ZSW2.9
Reserved
ZSW2.10
1 = Pulses enabled
ZSW2.11
Reserved
ZSW2.12
Slave sign-of-life, bit 0
ZSW2.13
Slave sign-of-life, bit 1
ZSW2.14
Slave sign-of-life, bit 2
ZSW2.15
Slave sign-of-life, bit 3
<1> These signals are automatically interconnected for clock-cycle synchronous operation.
1
2
PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
PROFIdrive - ZSW2 status word interconnection (p2038 = 0)
Meaning
3
4
Interconnection
[Function diagram]
parameters
internal control word
p2081[0] = r0051.0
-
p2081[1] = r0051.1
-
-
-
-
-
-
-
p2081[5] = r2139.11
[2548.6]
p2081[6] = r2139.12
[2548.6]
-
-
p2081[8] = r1406.8
[2520.6]
-
-
p2081[10] = r0899.11
[2503.7]
-
-
Implicitly interconnected
-
5
6