2 Parameters
2.2 List of parameters
r2229
Technology controller number actual / Tec_ctrl No. act
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: -
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
-
CU250S_V_PN
(Tech_ctrl)
Description:
Displays the number of the selected fixed setpoint of the technology controller.
Dependency:
Refer to: r2224
p2230[0...n]
Technology controller motorized potentiometer configuration / Tec_ctr mop config
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
-
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the configuration for the motorized potentiometer of the technology controller.
Bit field:
Bit
00
02
03
04
Dependency:
Refer to: r2231, p2240
Notice:
The following prerequisites must be fulfilled in order to be able to save the setpoint in a non-volatile fashion:
- Firmware with V2.3 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
Note:
For bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1: The setpoint for the motorized potentiometer is saved and after ON is entered using r2231. In order to save in a
non-volatile fashion, bit 03 should be set to 1.
For bit 02:
0: Without initial rounding-off
1: With initial rounding-off.
The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is a sensitive way of
specifying small changes (progressive reaction when keys are pressed). The jerk for initial rounding is independent
of the ramp-up time and only depends on the selected maximum value (p2237).
It is calculated as follows:
r = 0.0001 x max(p2237, |p2238|) [%] / 0.13^2 [s^2]
The jerk is effective until the maximum acceleration is reached (a_max = p2237 [%] / p2247 [s] or a_max = p2238 [%]
/ p2248 [s]), after which the drive continues to run linearly with constant acceleration.
The higher the maximum acceleration (the lower that p2247 is), the longer the ramp-up time increases with respect to
the set ramp-up time.
For bit 03:
0: Non-volatile data save deactivated.
1. The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1).
For bit 04:
When the bit is set, the ramp-function generator is computed independent of the pulse enable. The actual output
value of the motorized potentiometer is always in r2250.
368
Signal name
Data save active
Initial rounding-off active
Non-volatile data save active for p2230.0 =
1
Ramp-function generator always active
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7950
Factory setting
-
Data type: Unsigned32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
0000 0100 bin
0 signal
No
No
No
No
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
FP
-
-
-
-