Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0026 sets itself to the lower value of the pulsating DC link voltage.
r0027
CO: Absolute actual current smoothed / Motor current
Access level: 2
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
r0028
Modulation depth smoothed / Mod_depth smth
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the smoothed actual value of the modulation depth.
Dependency:
Refer to: r0074
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0029
Current actual value field-generating smoothed / Id_act smooth
Access level: 4
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the smoothed field-generating actual current.
Dependency:
Refer to: r0076
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0030
Current actual value torque-generating smoothed / Iq_act smooth
Access level: 4
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [%]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6799, 8850,
8950
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6799, 8950
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [Arms]
29