r1773[0...1]
Motor model slip speed / MotMod slip
Access level: 4
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays estimated (speed) signals of the motor model.
r1773[0]: Displays the estimated (mechanical) slip of the motor model.
r1773[1]: Displays the estimated input speed of the motor model.
Index:
[0] = Slip speed estimated
[1] = Speed estimated
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1774[0...n]
Motor model offset voltage compensation alpha / MotMod offs comp A
Access level: 4
Can be changed: U, T
Unit group: -
Min
-5.000 [V]
Description:
Sets the offset voltage in the alpha direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The value is pre-set during the rotating measurement.
p1775[0...n]
Motor model offset voltage compensation beta / MotMod offs comp B
Access level: 4
Can be changed: U, T
Unit group: -
Min
-5.000 [V]
Description:
Sets the offset voltage in the beta direction; this compensates the offset voltages of the drive converter/inverter at low
speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The value is pre-set during the rotating measurement.
r1776[0...6]
Motor model status signals / MotMod status sig
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the internal status signals of the motor model.
Index 0: Changeover ramp between current and voltage models
Index 1: Changeover ramp for model feedback (only for induction motors without encoder)
Index 2: Changeover ramp for zero frequency range (only for induction motors without encoder)
Index 3: Transition ramp actual speed from speed setpoint to model value (SESM without encoder)
Index 4: Speed controller enable (SESM without encoder)
Index 5: Transition ramp between current and voltage models (SESM without encoder)
Index 6: Transition ramp for EMF deviation at PLL input (PMSM without encoder)
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
5.000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
5.000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.000 [V]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.000 [V]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
-