Siemens SINAMICS G120 List Manual page 202

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
r1114
CO: Setpoint after the direction limiting / Setp after limit
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
p1115
Ramp-function generator selection / RFG selection
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the ramp-function generator type.
Value:
0:
1:
Note:
Another ramp-function generator type can only be selected when the motor is at a standstill.
r1119
CO: Ramp-function generator setpoint at the input / RFG setp at inp
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the setpoint at the input of the ramp-function generator.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
p1120[0...n]
Ramp-function generator ramp-up time / RFG ramp-up time
Access level: 1
Can be changed: C(1), U, T
Unit group: -
Min
0.000 [s]
Description:
The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency:
Refer to: p1082, p1123
Note:
The ramp-up time can be scaled via connector input p1138.
The parameter is adapted during the rotating measurement (p1960 > 0). This is the reason that during the rotating
measurement, the motor can accelerate faster than was originally parameterized.
For U/f control and sensorless vector control (see p1300), a ramp-up time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
202
Basic ramp-function generator
Extended ramp-function generator
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
999999.000 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3001, 3040, 3050
Factory setting
- [rpm]
Data type: Integer16
Dyn. index: -
Func. diagram: 3001, 3080
Factory setting
1
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3050, 3070, 6300,
8022
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3060, 3070
Factory setting
10.000 [s]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890