2 Parameters
2.2 List of parameters
p3324[0...n]
Fluid flow machine power point 3 / Fluid_mach P3
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 3 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3325[0...n]
Fluid flow machine speed point 3 / Fluid_mach n3
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 3 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3326[0...n]
Fluid flow machine power point 4 / Fluid_mach P4
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 4 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3327[0...n]
Fluid flow machine speed point 4 / Fluid_mach n4
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 4 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
452
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
77.00
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
50.00
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
92.00
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
75.00