p2658
BI: EPOS position actual value valid feedback signal / Pos valid feedback
CU250S_V (EPOS)
Access level: 3
CU250S_V_CAN
Can be changed: T
(EPOS)
Unit group: -
CU250S_V_DP
Min
(EPOS)
-
CU250S_V_PN
(EPOS)
Description:
Sets the signal source for the feedback signal "position actual value is valid".
BI: p2658 = 1 signal
The position actual value received via CI: p2657 is valid.
BI: p2658 = 0 signal
The position actual value received via CI: p2657 is invalid.
Dependency:
Refer to: r2526, p2657
Note:
While a 0 signal is present, the position setpoint (p2665) is held at the value of 0.
p2659
BI: EPOS referencing active feedback signal / Ref act fdbk
CU250S_V (EPOS)
Access level: 3
CU250S_V_CAN
Can be changed: T
(EPOS)
Unit group: -
CU250S_V_DP
Min
(EPOS)
-
CU250S_V_PN
(EPOS)
Description:
Sets the signal source for the feedback signal "referencing active".
BI: p2659 = 1 signal
Referencing is active.
BI: p2659 = 0 signal
Referencing is not active.
Dependency:
Refer to: r2526
p2660
CI: EPOS measured value referencing / Meas val ref
CU250S_V (EPOS)
Access level: 3
CU250S_V_CAN
Can be changed: T
(EPOS)
Unit group: -
CU250S_V_DP
Min
(EPOS)
-
CU250S_V_PN
(EPOS)
Description:
Sets the signal source for the measured value for the function "referencing".
Dependency:
Refer to: r2523
p2661
BI: EPOS measured value valid feedback signal / MeasVal valid fdbk
CU250S_V (EPOS)
Access level: 3
CU250S_V_CAN
Can be changed: T
(EPOS)
Unit group: -
CU250S_V_DP
Min
(EPOS)
-
CU250S_V_PN
(EPOS)
Description:
Sets the signal source for the feedback signal "measured value valid".
BI: p2661 = 1 signal
The measured value received via CI: p2660 is valid.
BI: p2661 = 0 signal
The measured value received via CI: p2660 is invalid.
Dependency:
Refer to: r2526, p2660
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3635
Factory setting
2526.0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3612
Factory setting
2526.1
Data type: U32 / Integer32
Dyn. index: -
Func. diagram: 3612, 3614
Factory setting
2523[0]
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3612, 3614, 3615
Factory setting
2526.2
431