Download Print this page

Siemens SINAMICS G120 List Manual page 399

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

p2549
BI: LR enable 1 / Enable 1
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the position controller enable 1.
Dependency:
Refer to: r0899, p2550
Note:
The position controller is enabled by the following AND logic operation:
- BI: p2549
- BI: p2550
p2550[0...n]
BI: LR enable 2 / Enable 2
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the position controller enable 2.
Dependency:
Refer to: p2549
Note:
The position controller is enabled by the following AND logic operation:
- BI: p2549
- BI: p2550
p2551
BI: LR setpoint signal fixed / Mess setp fixed
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the "setpoint fixed" signal.
BI: p2551 = 1 signal:
The end of the positioning operation on the setpoint side is signaled and the positioning and standstill monitoring
activated.
BI: p2551 = 0 signal:
The start of a positioning operation or tracking mode on the setpoint side is signaled and the positioning and standstill
monitoring deactivated.
Dependency:
Refer to: p2554, r2683
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 4015
Factory setting
899.2
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 4015
Factory setting
1
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 4020
Factory setting
2683.2
399

Hide quick links:

Advertisement