Siemens SINAMICS G120 List Manual page 158

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
CU250S_V
Access level: 2
CU250S_V_CAN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
p0811
BI: Command data set selection CDS bit 1 / CDS select., bit 1
Access level: 2
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to select the Command Data Set bit 1 (CDS bit 1).
Dependency:
Refer to: r0050, p0810, r0836
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
p0819[0...2]
Copy Drive Data Set DDS / Copy DDS
Access level: 2
Can be changed: C(15)
Unit group: -
Min
0
Description:
Copies one Drive Data Set (DDS) into another.
Index:
[0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Dependency:
Refer to: r3996
Notice:
When the drive data sets are copied, short-term communication interruptions may occur.
Note:
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In index 1, enter the drive data set data that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
p0820[0...n]
BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level: 3
Can be changed: C(15), T
Unit group: -
Min
-
Description:
Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
158
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 8560
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 8560
Factory setting
0
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8565
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 8565, 8575
Factory setting
0
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890