r2266
CO: Technology controller actual value after filter / Tec_ctr act aftFlt
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: -
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
- [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
p2268
Technology controller lower limit actual value / Tec_ctrl l_lim act
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value falls below this lower limit, this results in fault F07426.
p2269
Technology controller gain actual value / Tech_ctrl gain act
CU250S_V (Tech_ctrl)
Access level: 3
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the scaling factor for the actual value of the technology controller.
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2271
Note:
For 100%, the actual value is not changed.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
500.00 [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
-100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]