Download Print this page

Siemens SINAMICS G120 List Manual page 749

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Current
I I
U
I
AI 0/1
Voltage
U
U
Kl. 3
(Kl. 10)
AI 0/1
+
U
I
<1>
Kl. 4
(Kl. 11)
<5>
0 ... 20 mA
-10 ... +10 V
<1>
Differential Input!
For an input signal referred to ground, Kl. 4 (Kl. 11) must be connected to reference potential M.
Notice:
The voltage between inputs and between input and the ground point must not exceed 35 V.
When the load resistor is switched in (DIP switch in position I), the voltage between the input terminals
must not exceed 10 V or the impressed current 80 mA. If this is not observed, the input will be damaged.
<2>
For p0756 = 2, 3 the units are mA.
Kl. = Terminal
For p0756 = 0, 1, 4 the units are V.
1
2
Input/Output Terminals
Analog inputs 0 ... 1 (AI 0 ... AI 1)
p0756[0..1] (4)
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
1
20 mA
0
Hardware smoothing
100 μs
A
Type switching
Analog input
D
CU AI sim setp
-50.000 ... 2000.000
p0798[0..1] (0.000)
<2>
Sampling time of the AI: 4 ms
3
4
<2> <3>
<4>
CU AI type
0 ... 4
3
20 mA
3
<2>
CU AI U/I_inp act
r0752
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
CU AI char y2
-1000.00 ... 1000.00 [%]
0
p0760[0..1] (100.00)
CU AI char y1
1
-1000.00 ... 1000.00 [%]
p0758[0..1] (0.00)
CU AI value in % [%]
r0755
[0..1]
5
fp_2251_97_52.vsd
05.09.2017
CU WireBrkThresh
CU wire brk t_del
0.00 ... 20.00
0 ... 1000 [ms]
p0761[0..1] (2.00)
p0762[0..1] (100)
T
0
<2>
<2>
CU AI char x1
CU AI char x2
-50.000 ... 160.000
-50.000 ... 160.000
p0757[0..1] (0.000)
p0759[0..1] (10.000) CU AI T_smooth
0.0 ... 1000.0 [ms]
y
[%]
y
2
[%]
x
y
x
x
x
1
2
y
1
Scaling
x
Reference quantities
1
p2000 ... r2004
x
x
2
x
· x
1
2
100 %
<3>
Possible settings p0756[0] and p0756[1]:
= 0: 0 V ... +10 V
= 1: +2 V ... +10 V with monitoring
= 2: 0 mA ... +20 mA
= 3: 4 mA ... +20 mA with monitoring
= 4: -10 V ... +10 V (Default for AI 0 and AI 1)
<4>
Wire breakage sensing only activated when p0756 = 1, 3.
<5>
Values in brackets --> AI 1
6
7
Function diagram
G120 CU250S-2
V4.7.9
CU AI status word
r0751
F03505
"Wire
breakage"
p0753[0..1] (0.0)
y
8
- 2251 -