Siemens SINAMICS G120 List Manual page 15

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Table 2-1
PM250
PM260
PM340
Access level
Specifies the minimum access level required to be able to display and change the relevant
parameter. The required access level can be set using p0003.
The system uses the following access levels:
• 1: Standard (not adjustable, included in p0003 = 3)
• 2: Extended (not adjustable, included in p0003 = 3)
• 3: Expert
• 4: Service
Note
Parameter p0003 is CU-specific (belongs to the Control Unit).
A higher access level will also include the functions of the lower levels.
Calculated
Specifies whether the parameter is influenced by automatic calculations.
p0340 determines which calculations are to be performed:
• p0340 = 1 includes the calculations from p0340 = 2, 3, 4, 5.
• p0340 = 2 calculates the motor parameters (p0350 ... p0360, p0625).
• p0340 = 3 includes the calculations from p0340 = 4, 5.
• p0340 = 4 only calculates the controller parameters.
• p0340 = 5 only calculates the controller limits.
Note
For p3900 > 0, p0340 = 1 is also called automatically.
After p1900 = 1, 2, p0340 = 3 is also called automatically.
Parameters with a reference to p0340 after "Calculated" depend on the Power Module being
used and the motor. In this case, the values at "Factory setting" do not correspond to the actual
values because these values are calculated during the commissioning. This also applies to the
motor parameters.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Information in the "CU variants" field, continued
CU/PM variants
Power Module (3 AC 400 V with energy recovery)
Power Module (3 AC 690 V with energy recovery)
Power Module for standard applications with dynamic braking
(1 AC 230 V)
Parameters with this access level are password protected.
2.1 Overview of parameters
Meaning
2 Parameters
15

Hide quick links: