Download Print this page

Siemens SINAMICS G120 List Manual page 157

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

r0807.0
BO: Master control active / PcCtrl active
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Bit field:
Bit
00
Dependency:
Refer to: p0806
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The commissioning software (drive control panel) uses the master control, for example.
p0809[0...2]
Copy Command Data Set CDS / Copy CDS
Access level: 2
Can be changed: T
Unit group: -
Min
0
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Dependency:
Refer to: r3996
Notice:
When the command data sets are copied, short-term communication interruptions may occur.
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
CU250S_V_DP
Access level: 2
CU250S_V_PN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Signal name
Master control active
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8560
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 8560
Factory setting
722.3
FP
3030,
6031
157

Hide quick links:

Advertisement

loading