2.2
List of parameters
Product: SINAMICS G120S, Version: 4710100, Language: eng
Objects: CU250S_V, CU250S_V_CAN, CU250S_V_DP, CU250S_V_PN
r0002
Drive operating display / Drv op_display
Access level: 1
Can be changed: -
Unit group: -
Min
0
Description:
Operating display for the drive.
Value:
0:
10:
11:
12:
13:
14:
15:
16:
17:
18:
19:
21:
22:
23:
31:
35:
41:
42:
43:
44:
45:
46:
60:
70:
200:
250:
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
STO: Safe Torque Off
p0003
Access level / Acc_level
Access level: 1
Can be changed: C, U, T
Unit group: -
Min
3
Description:
Sets the access level to read and write parameters.
Value:
3:
4:
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Operation - everything enabled
Operation - set "enable setpoint" = "1" (p1142, p1152)
Operation - set "enable speed controller" = "1" (p0856)
Operation - RFG frozen, set "RFG start" = "1" (p1141)
Operation - set "enable RFG" = "1" (p1140)
Oper. - MotID, excit. running and/or brake opens, SS2, STOP C
Operation - open brake (p1215)
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
Operation - braking with OFF3 can only be interrupted with OFF2
Operation - brake on fault, remove fault, acknowledge
Operation - armature short-circ./DC brake act. (p1230, p1231)
Ready for operation - set "Enable operation" = "1" (p0852)
Ready for operation - de-magnetizing running (p0347)
Ready for operation - set "Infeed operation" = "1" (p0864)
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
Switching-on inhibited - carry out first commissioning (p0010)
Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
Switching-on inhibited - rectify fault, acknowledge fault, STO
Switching-on inhibited - exit commissioning mode (p0009, p0010)
Drive object de-activated/not operational
Initialization
Wait for booting/partial booting
Device signals a topology error
Expert
Service
Calculated: -
Scaling: -
Unit selection: -
Max
250
Calculated: -
Scaling: -
Unit selection: -
Max
4
2 Parameters
2.2 List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
3
25