Download Print this page

Siemens SINAMICS G120 List Manual page 386

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
p2510[0...3]
BI: LR selecting measuring probe evaluation / MT_eval select
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source to select the measuring probe.
1 signal = measuring probe 2 is activated for BI: p2509 = 0/1 edge.
0 signal = measuring probe 1 is activated for BI: p2509 = 0/1 edge.
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency:
Refer to: p2502, p2509, p2511
Note:
The following BICO interconnection is established as standard:
BI: p2509[0] = r2684.1
The measuring probe is selected at the 0/1 signal transition at r2684.1 (flying referencing active).
p2511[0...3]
BI: LR measuring probe evaluation edge / MT_eval edge
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the edge evaluation of the measuring probe.
1 signal = falling edge of the measuring probe (p2510) is activated for BI: p2509 = 0/1 edge.
0 signal = rising edge of the measuring probe (p2510) is activated for BI: p2509 = 0/1 edge.
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency:
Refer to: p2502, p2509, p2510
p2512[0...3]
BI: LR pos. actual value preprocessing activate corr. value (edge) /
ActVal_prepCorrAct
CU250S_V (Position
Access level: 1
control)
Can be changed: T
CU250S_V_CAN
Unit group: -
(Position control)
Min
CU250S_V_DP
-
(Position control)
CU250S_V_PN
(Position control)
Description:
Sets the signal source for the function "activate position actual value preprocessing, corrective value (edge)".
0/1 signal:
The correction value available via CI: p2513 is activated.
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
386
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3615, 4010
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3615, 4010
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 4010, 4015
Factory setting
[0] 2684.7
[1] 0
[2] 0
[3] 0
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890

Hide quick links:

Advertisement

loading