Siemens SINAMICS G120 List Manual page 191

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Recommendation:
Interconnect the signal with main setpoint (p1070).
Dependency:
Refer to: p1070
Note:
For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
suppress pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
p1051[0...n]
CI: Speed limit RFG positive direction of rotation / n_limit RFG pos
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the speed limit of the positive direction on the ramp-function generator input.
Note:
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
p1052[0...n]
CI: Speed limit RFG negative direction of rotation / n_limit RFG neg
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the speed limit of the negative direction on the ramp-function generator input.
Note:
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
CU250S_V_DP
Access level: 3
CU250S_V_PN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for jog 1.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
CU250S_V
Access level: 3
CU250S_V_CAN
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for jog 1.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3050
Factory setting
9733[0]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3050
Factory setting
9733[1]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501, 3030
Factory setting
[0] 0
[1] 722.0
[2] 0
[3] 0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501, 3030
Factory setting
0
191