Download Print this page

Siemens SINAMICS G120 List Manual page 135

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

Dependency:
For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
The signal is not suitable as a process quantity and may only be used as a display quantity.
p0628[0...n]
Motor overtemperature rotor / Mot T_over rotor
Access level: 4
Can be changed: C(3), U, T
Unit group: 21_2
Min
20 [K]
Description:
Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature in the motor
temperature model 2 (p0612.1 = 1).
Dependency:
For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
r0630[0...n]
Mot_temp_mod ambient temperature / Mod T_ambient
Access level: 4
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Displays the ambient temperature of the motor temperature model (models 2 and 3).
r0631[0...n]
Mot_temp_mod stator iron temperature / Mod T_stator
Access level: 4
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Displays the stator iron temperature of the motor temperature model (models 2 and 3).
Note:
For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
r0632[0...n]
Mot_temp_mod stator winding temperature / Mod T_winding
Access level: 2
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Displays the stator winding temperature of the motor temperature model.
Dependency:
Refer to: F07011, A07012, A07910
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: p0340 = 1,2
Scaling: -
Unit selection: p0505
Max
200 [K]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8018
Factory setting
100 [K]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8018
Factory setting
- [°C]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8018
Factory setting
- [°C]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017, 8018
Factory setting
- [°C]
135