Siemens SINAMICS G120 List Manual page 370

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
p2238[0...n]
Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2237
p2240[0...n]
Technology controller motorized potentiometer starting value / Tec_ctrl mop start
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
-200.00 [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency:
Refer to: p2230
r2245
CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: -
(Tech_ctrl)
Unit group: 9_1
CU250S_V_DP
Min
(Tech_ctrl)
- [%]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency:
Refer to: r2250
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
CU250S_V (Tech_ctrl)
Access level: 2
CU250S_V_CAN
Can be changed: U, T
(Tech_ctrl)
Unit group: -
CU250S_V_DP
Min
(Tech_ctrl)
0.0 [s]
CU250S_V_PN
(Tech_ctrl)
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
370
Calculated: -
Scaling: -
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
-100.00 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
0.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7954
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
10.0 [s]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890