Download Print this page

Siemens SINAMICS G120 List Manual page 292

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

2 Parameters
2.2 List of parameters
r1791
Motor model Lh adaptation switch-on frequency / MotMod Lh f_on
Access level: 4
Can be changed: -
Unit group: -
Min
- [Hz]
Description:
Displays the switch-on stator frequency/ primary section frequency for the Lh adaptation for the induction motor
(ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
r1792
Motor model Lh adaptation switch-on slip / MotMod Lh fslip
Access level: 4
Can be changed: -
Unit group: -
Min
- [Hz]
Description:
Displays the switch-on slip frequency for the Lh adaptation for the induction motor (ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1795[0...n]
Motor model kT adaptation integral time / MotMod kT Tn
Access level: 4
Can be changed: U, T
Unit group: -
Min
10 [ms]
Description:
Sets the integral time of the kT adaptation of the motor model for a permanent-magnet synchronous motor (PMSM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
r1797[0...n]
Motor model kT adaptation corrective value / MotMod kT corr
Access level: 4
Can be changed: -
Unit group: -
Min
- [Nm/A]
Description:
Displays the corrective value of the kT adaptation of the motor model for a permanent-magnet synchronous motor
(PMSM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0826, p1780
Note:
The display of the inactive data sets is only updated when changing over the data set.
p1800[0...n]
Pulse frequency setpoint / Pulse freq setp
Access level: 2
Can be changed: U, T
Unit group: -
Min
2.000 [kHz]
Description:
Sets the pulse frequency for the converter.
This parameter is pre-set to the rated converter value when the drive is first commissioned.
Dependency:
Refer to: p0230
292
Calculated: -
Scaling: -
Unit selection: -
Max
- [Hz]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Hz]
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Nm/A]
Calculated: -
Scaling: -
Unit selection: -
Max
16.000 [kHz]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Hz]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Hz]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6731
Factory setting
100 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6731
Factory setting
- [Nm/A]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8021
Factory setting
4.000 [kHz]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890

Hide quick links:

Advertisement

loading