r0208
Rated power unit line supply voltage / PU U_rated
Access level: 2
Can be changed: -
Unit group: -
Min
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400: 380 - 480 V +/-10 %
r0208 = 500: 500 - 600 V +/-10 %
r0208 = 690: 660 - 690 V +/-10 %
r0209[0...4]
Power unit maximum current / PU I_max
Access level: 3
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
p0210
Drive unit line supply voltage / U_connect
Access level: 3
Can be changed: C(2), T
Unit group: -
Min
1 [V]
Description:
Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency:
Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
Notice:
If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically deactivated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
Note:
Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 230 V:
- p0210 = 200 ... 240 V
U_rated = 400 V:
- p0210 = 380 ... 480 V
U_rated = 690 V:
- p0210 = 500 ... 690 V
p0219
Braking resistor braking power / R_brake P_brake
PM240
Access level: 3
Can be changed: C(1, 2), T
Unit group: 14_6
Min
0.00 [kW]
Description:
Sets the braking power of the connected braking resistor.
Dependency:
Refer to: p1127, p1240, p1280, p1531
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Calculated: -
Scaling: -
Unit selection: -
Max
- [Vrms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
63000 [V]
Calculated: -
Scaling: -
Unit selection: p0100
Max
20000.00 [kW]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8750, 8850, 8950
Factory setting
- [Arms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
400 [V]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.00 [kW]
55