2 Parameters
2.2 List of parameters
Dependency:
Refer to: p10001, p10003, p10007, p10047
Note:
The test stop is only performed if the safety output of the Control Unit is being used (see p10042).
p10047
SI Motion F-DO test stop mode (processor 1) / SI F-DO testmodeP1
Access level: 3
Can be changed: C(95)
Unit group: -
Min
1
Description:
Sets the test stop mode for the safety digital output (F-DO)
Value:
1:
2:
3:
Dependency:
Refer to: p10001, p10003, p10007, p10046
Note:
The test stop is only performed if the safety output is being used (see p10042).
r10049
SI Motion F-DI monitoring status (processor 1) / SI F-DI status P1
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the monitoring status of the fail-safe digital inputs (F-DI).
The F-DIs that are being used by the Safety Integrated functions are displayed.
If the module used has fewer than 3 F-DIs, "Freely available" is displayed for the F-DIs which are not in use.
Bit field:
Bit
00
01
02
Dependency:
p10006 / p10106
p10022 / p10122
p10023 / p10123
p10026 / p10126
p10030 / p10130
p10031 / p10131
Refer to: r10149
p10050
SI Motion PROFIsafe F-DI transfer (processor 1) / SI Ps F-DI tran P1
Access level: 3
Can be changed: C(95)
Unit group: -
Min
-
Description:
Setting for the transfer and evaluation of fail-safe digital inputs (F-DI) via PROFIsafe.
The safe state of the selected F-DIs is transferred to the F-control via PROFIsafe. The F-DIs are monitored for
discrepancies. Discrepancy faults can be acknowledged via PROFIsafe.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p10150
Note:
F-DI: Fail-safe Digital Input
602
Test mode 1 evaluation of int. diagnostic signal (passive load)
Test mode 2 read back F-DO in DI (relay circuit)
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Signal name
F-DI 0
F-DI 1
F-DI 2
Signal name
F-DI 0 processor 1
F-DI 1 processor 1
F-DI 2 processor 1
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Safety monitored
Safety monitored
Safety monitored
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Transfer
Transfer
Transfer
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
2
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
Freely available
Freely available
Freely available
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0000 bin
0 signal
No transfer
No transfer
No transfer
SINAMICS G120 CU250S-2 Control Units