Parameters/Address Space; Parameters; Explanation Of The Parameters - Siemens SIMATIC ET 200AL Manual

10-link digital output module dq 8x24vdc/2a 8xm12
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Parameters/address space

4.1

Parameters

The following table shows the parameters for the DQ 8x24VDC/2A 8xM12 IO-Link digital
output module.
Table 4- 1
Parameters
Parameters
Diagnostics: Missing load volt-
age 2L+
Diagnostics: Short-circuit to
ground
Reaction to CPU/master STOP
Substitute value channel
4.2

Explanation of the parameters

Diagnostics: Missing load voltage 2L+
Enabling of the diagnostics for missing or insufficient load voltage 2L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics for short-circuit of the output to ground.
Reaction to CPU/master STOP
With this parameter, you set the reaction of the digital outputs of the module after a
CPU/master STOP:
• Shut down: The digital output is de-energized.
• Keep last value: The last value of the digital output remains activated.
• Output substitute value: The module outputs a configured substitute value.
Substitute value channel
With this parameter, you set substitute values for the digital outputs.
IO-Link digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BL0)
Equipment Manual, 08/2021, A5E47926730-AB
Value range
Value
Dec
Hex
.
.
Disable
0
0
Enable
255 FF
Disable
0
0
Enable
255 FF
Shutdown
0
0
Keep last value
2
2
Output substi-
3
3
tute value
0
0
0
1
255 FF
Default
Scope
Disable
Module
Disable
Module
(Short-circuit of an
output to ground)
Shutdown
Module
0
Channel
4
ISDU
ISDU
index
subindex
(decimal)
(decimal)
131
1
131
2
131
3
131
4 ... 11
15