Commissioning Using The Display And Operator Unit - Siemens SIMODRIVE 611 universal Function Manual

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

4 Commissioning
4.4

Commissioning using the display and operator unit

4.4
Commissioning using the display and operator unit
START
S
Connect–up the unit
S
Check the connections (refer to Chap. 2.3.1)
S
De–energize terminal 663 (pulses are then
not enabled)
Power–up the unit (power ON)
Already
commissioned?
"_ _ _ r u n"
displayed?
Request
no
new
commissioning?
End
(cyclic
operation)
Establish the boot state
S
Remove write protection (P0651 = 4)
S
Establish the boot state (P0659 = 0)
S
Start to write into the FEPROM
(P0652 = 1) and then wait until the write
operation has been completed (P0652
= 0)
S
Execute a HW POWER–ON RESET or
POWER OFF ! ON
1. Axxxx, bxxxx: Parameters, drive A, B
2. Only set, if there is no automatic
power module identification available
(refer to Chapter 4.6)
3. The parameter value is changed using these keys
4. If drive B is not used, then b0700 = 0 (drive B inactive) and b0659 = 0 –> 1 (boot)
5. Set the PROFIBUS node address ––> refer to Chapter 5.7.2
Fig. 4-3
Commissioning using the display and operator unit (Part 1 of 3)
4-128
no
yes
no
Is
Oper. control
yes
Key P (+/–)
Key P, +
Key P (+/–)
Key P, +
yes
Key P (+/–)
Key P, +
Key P (+/–)
Key P, +
Key P, +, P
Key P
3
Press the + and – keys simultaneously (up to b0659)
Press the – key
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Is the "E– ..."? displayed flashing or
is the display inactive?
Remove the cause!
(refer to Chapter 7)
3
Is a
1)
A1106
or b1106
displayed?
yes
Execute the hardware configuration
Display Description
A1106 Power module code No.
3)
Set the code (refer to Chapter A.2)
A1102 Motor code number
3)
Set the code (refer to Chapter A.3)
A1006 Encoder code number
3)
Set the code (refer to Chapter A.4)
A0700 Operating mode
3)
Set the BM (refer to Chapter 4.6)
A0659 Boot
Boot (P0659 = 0 –> 1)
A0659 or b0659 is displayed
Are both
drives
configured?
no
up to b1106 in the display
E Siemens AG 2005 All Rights Reserved
01.99
no
1)
2)
5)
yes
1
4)
Continue on the
next page

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents