Siemens SIMODRIVE 611 universal Function Manual page 515

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

01.99
04.05
08.01
! 611ue diff !
Table 6-49
List of output signals, continued
Signal name, description
Control requested/no control possible
The status of the DP slave is signaled to the DP master using this output signal.
1 signal
Control requested
The DP master is requested to accept control.
Recommendation:
As a result of this output signal, the DP master should accept control and control bit
STW1.10 "Control requested/not control requested" should be set to "1".
Note: (from SW 4.1)
For a two–axis drive, this bit is only influenced at axes which also retrieve data from a
publisher via slave–to–slave communications
(refer to Chapter 5.10).
0 signal
Control not possible
The DP master is signaled that control is not possible. This is, for example, the case for
the following states:
– the "DP slave 611U" has still not irun–up
– the "SimoCom U" tool has taken–over the master control
– the clock–cycle synchron. PROFIBUS no longer operates with clock cycle synchronism
– for slave–to–slave communications, not all of the links have been established to the
publisher (from SW 4.1)
Comparison value reached/comparison value not
reached
The output signal indicates whether the comparison value, set using P1418:8, has been fallen below.
1 signal
actual value > comparison value (P1418:8)
0 signal
actual value < comparison value (P1418:8)
Comparison value
1 signal
Comparison value reached
0 signal
Note:
S
The output signal corresponds to the | n
S
In n–set operation, this signal occupies the PROFIBUS bit ZSW1.10 if spindle positioning has not
been selected (from SW 5.1) (P0125=0). For the "spindle positioning" function (from SW 5.1), the "ref-
erence position reached/outside reference position" signal occupies ZSW1.10 (P0125=1), refer to
output signal Function No. 60.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.4
Input/output terminals of the control board
Fct. No.
| n
|
act
Actual value
Actual value
>
<
comparison
comparison
value
value
| < n
signal with inverted logic.
act
min
6 Description of the Functions
Operating
mode
n–set
pos
PROFIBUS bit
x
x
ZSW1.9
x
ZSW1.10
Fixed hysteresis= 2 RPM
P1418:8
t
Actual value
>
comparison
value
6
6-515

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents