Connecting-Up The Power Module - Siemens SIMODRIVE 611 universal Function Manual

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

2 Installing and Connecting-Up
2.2
Connecting–up
2.2.3
Connecting–up the power module
Table 2-2
Overview of the interfaces
Terminals
No.
Desig-
nation
Motor connections
U2
A1
Motor connection
for drive A
V2
W2
U2
A2
Motor connection
for drive B
V2
(only for 2–axis
W2
power modules)
PE
Protective conductor
DC link
P600
DC link
M600
Equipment bus
X151
Equipment bus
1) O: Output; I: Input; IO: Input/output
!
2-70
Function
Type
1)
1)
O
O
I
IO
IO
Warning
If a contactor is used between the motor and the power module, then it
must be ensured that this contactor is only switched in a no–current
condition (power circuit).
Powering–down:
When terminal 663 (pulse cancellation) is simultaneously de–energized
and the coil of the power contactor, this condition is maintained. The
pulses are almost instantaneously canceled, the contactor contacts are
then in a no–current condition, and switch somewhat later due to the
contact delay.
Powering–up:
Terminal 663 may only be energized if all of the main contacts of the
power contactor are closed (e.g. terminal 663 is switched through an
auxiliary contact of the power contactor).
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Technical data
Note:
Additional information on connecting–up the power
module, technical data as well as interface over-
view are included in:
view are included in:
Reference:
/PJU/ SIMODRIVE 611
Configuration Manual,
Drive Converters
Chapter "Power module"
0 V
Screw
Busbar
Ribbon cable:
34–pole
Voltages:
various
Signals:
various
E Siemens AG 2005 All Rights Reserved