6 Description of the Functions
6.6

Analog inputs

6.6
Analog inputs
Description
6-528
For "SIMODRIVE 611 universal", there are two analog inputs for each
drive.
In the "speed/torque setpoint" mode, the setpoint can be entered for
the following functions via these analog inputs:
S
Speed Speed–controlled operation (n
For the n
mode, the analog voltage at terminal 56.x/14.x and/or
set
terminal 24.x/20.x is used as speed setpoint.
S
Torque: Open–loop torque controlled operation (M
For the M
mode the analog voltage at terminal 56.x/14.x and/or
set
terminal 24.x/20.x is used as torque setpoint.
Open–loop torque control is used, if
– the speed controller is implemented in a higher–level control, or
– the master/slave functionality is used
S
Torque/power reduction (M
It may be necessary to reduce the maximum drive torque to protect
the machine components. The following possibilities exist:
– Permanent torque limiting
This limit function can be set via parameters P1230 or P1235
(refer to Chapter 6.1.8).
– Variable torque limiting
In this case, analog input 2 is set to M
voltage at terminal 24.x/20.x is used to continuously reduce the
torque.
In the "positioning" mode, a setpoint can be entered for the velocity
override via analog input 1.
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
operation)
set
mode)
red
mode and the analog
red
E Siemens AG 2005 All Rights Reserved
01.99
! not 611ue !
mode)
set