Invalid signal number
Cause
The signal number for the analog output is not permissible.
An analog value can be output for diagnostic, service and optimization
tasks
Term. 75.x/15, 16.x/15, DAC1, DAC2
Remedy
Enter valid signal number
(refer to the Description of Functions SIMODRIVE 611 universal)
Acknowledgement
not required
Stop response
STOP VII
866
Parameterizing error, current controller adaption
Cause
For the current controller adaption, the upper current limit (P1181) was
parameterized with a lower value than the lower current limit (P1180).
Adaption is de-activated when the parameterizing error is output.
Remedy
P1181 must contain a higher value than P1180.
Acknowledgement
not required
Stop response
STOP VII
867
Generator mode: Response voltage > shutdown
threshold
Cause
The sum of the values in P1631 + P1632 is greater than the value in
P1633.
Remedy
Appropriately change P1631, P1632 and P1633.
Note:
P1631 to P1633 being prepared
Acknowledgement
not required
Stop response
STOP VII
868
Generator mode: Response voltage > monitoring
threshold
Cause
The input value for the threshold voltage (P1631) is greater than the
value in P1630.
Remedy
Change the drive parameters.
Note:
P1630 and P1631 being prepared
Acknowledgement
not required
Stop response
STOP VII