Diagnostics Via Led Display On The Basic Unit And On The Operator Panel - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Commissioning and service
14.2.3

Diagnostics via LED display on the basic unit and on the operator panel

The basic units and the operating panel have three LEDs for displaying
specific device states:
LED
Device
Bus
Gen.
Fault
Table 14-4: Diagnostics via LED display
14-6
Status
Display
Description
Device
Green
Device is ready for
status
operation
Green –
Internal fault
flickering
Yellow
Memory module or
addressing plug
recognized, Test/Reset
buttons control the
memory module or
addressing plug
Yellow –
Memory module/
flashing
addressing plug read in;
factory settings
configured (duration: 3s)
Yellow –
Memory module
flickering
programmed (duration:
3s)
Red
Parameterization
incorrect (also Gen.
Fault on)
Basic unit defective
(also Gen. Fault on)
Red –
Memory module,
flashing
addressing plug,
expansion modules
defective (also Gen.
Fault on - flashing)
Off
Supply voltage too low
Bus
Off
Bus not connected or
status
bus fault
Green –
Baud rate recognized/
flashing
communication with
PC/programming device
Green
Communication with
PLC/PCS
Fault
Red
Fault pending; reset has
status
been saved
Red –
Fault pending; reset has
flashing
not been saved
Off
No fault
Corrective measures for
faults
Send back the basic unit
Parameterize again and
switch the control
voltage off and on again
Replace basic unit!
Reprogram/replace the
memory module,
replace the expansion
modules
Check whether the
supply voltage is
connected/switched on
Connect the bus or
check bus parameters
Rectify fault, e.g.
overload
Rectify fault, e.g.
overload
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03