Siemens SIMODRIVE 611 universal Function Manual page 705

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

01.99
04.05
833
PROFIBUS: No connection to the publisher \%u
Cause
Cyclic data transfer between this slave and a slave-to-slave commu-
nications publisher was still not started or was interrupted.
Examples:
– Bus connection interrupted
– Publisher failure
– Master runs up again
– The response monitoring (Watchdog) for this slave was de-activated
Supplementary info: PROFIBUS address of the publisher
Remedy
Check the publisher and bus connections to the publisher, to the
master and between the master and publisher.
if the watchdog is de-activated, activate the response monitoring for
this slave via Drive ES.
Acknowledgement
not required
Stop response
STOP VII
840
Teach-in for running traversing program
Cause
Teach-in was requested during a running traversing program.
Remedy
Exit the traversing program and re-request teach-in.
Acknowledgement
not required
Stop response
STOP VII
841
Teach-in for relative block
Cause
The traversing block as "teach in block" is relative instead of absolute.
Remedy
Change the traversing block mode "teach in block" from relative to ab-
solute.
Acknowledgement
not required
Stop response
STOP VII
842
Teach-in for a relative standard block
Cause
The traversing block as "teach in standard set", is relative instead of
absolute.
Remedy
Change the traversing block mode "teach in standard block" from rela-
tive to absolute.
Acknowledgement
not required
Stop response
STOP VII
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
via the parameterizing telegram (SetPrm) (Diagnostics: P1783:1
bit 3 = 0).
7 Fault Handling/Diagnostics
7.3
List of faults and warnings
7
7-705

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents